OVERVIEW
The FDE series RF admittance is a level gauge assembled by our company using the technology and production process of DE Corporation in the United States. This level gauge has the advantages of simple adjustment, high sensitivity, and wide applicability.
Technical Parameter
- Electronic unit
Power supply voltage: AC220V ± 10% 50Hz DC24V
Contact capacity: AC 220V 5 A DC24V 5 A
Power consumption: 4W
Environmental temperature: -40 ℃ -85 ℃
Temperature effect: 0.1PF/20 ℃
Sensitivity: 0.3PF
Repeatability: ≤± 1.6mm
Intrinsically safe type with safety barrier: LB803S - CASING
Standard cast aluminum shell
Explosion proof grade: Exd Ⅱ CT4-6
Protection level: IP66
Shell size: φ150 × 170mm - Probe rod material
316L、 Tetrafluoroethylene, ABS plastic, ceramics - The relationship between pressure and temperature
Room temperature type: atmospheric pressure, -150~250 ℃; 2.5MPa,≤150℃
High temperature type: 2.5MPa, ≤ 800 ℃; 6.3MPa,≤250℃